top of page
CATEGORIES
FEATURED PRODUCTS

Auto Setting Control Pack (FACP-11)

Introduction:

The FACP-11 Auto Setting Controll Pack is capable of controlling the actuator's open/close degree over a resolution of 200:1 by a control signal of 4-20mA dc or 2-10vdc.

Features & Specifications

Features:

  • Needless to adjust- fully automated

  • High rangeability of control - over 200:1 resolution

  • Additional function

         1. Fail mode (upon control signal loss)

              • Open - fail to open Stop - fail to stop

               Close -fail to close

         2. Self checking function

              • checking for limit switch checking for pot 

              • checking for motor

         3.lectronic brake control

         4. feedback output : 4~20mA 1%DC(RL:250ohm)

         5.small & lightweight


Electrical Specifications:

  • Power: 110vac or 220vac 50/60Hz

  • Control Signal Input : 4~ 20mA dc or 2~10vdc

  • Output Sibnal : 4~20mA 1%DC(RL:250ohm)

  • Calibration: Auto setting

  • Resolution: over 200


Power consumption:

Max 150W @110vac or 200W @220vac

Operation

Our modulating module is equipped with a blockage protection feature. If the actuator encounters a blockage, the module will automatically shut off the motor approximately 7 seconds after detection. Simultaneously, the yellow indicator lamp will flash rapidly, signaling that the actuator has entered Blockage Protection Mode.


To exit this mode, a reverse input signal must be provided. Upon receiving this signal, the actuator will deactivate the Blockage Protection Mode and resume normal operation.




1.Indicator explanations:

Green Lamp On - Actuator is Opening

Yellow Lamp On - Actuator is Operating 

Yellow Lamp Flashing Slowly - fully open/closed

Yellow Lamp Flashing Quickly - Fail check limit switch, potentiometer, etc.

Red Lamp On - Actuator is Closing


2.Auto Setting Switch:

Press and hold the Auto Setting Switch for 3 seconds to start the actuator's auto-calibration, where it cycles twice to find and confirm its open and close limit positions for precise operation.


3.Mode Switch Operation & Setting:

4. Output Adjust VR:

Fine-tune the "feedback output" for precise adjustment.


5. Limit Switch:

Input terminal where the digital limit is activated, indicated as "A."

 Limit switch common Close limit switch • Open limit switch


6. Motor & Potentiometer

 Motor common Open motor  Close motor • Ground

• Potentiometer P1  Potentiometer P2 • Potentiometer P3