CATEGORIES
FEATURED PRODUCTS
Auto Setting Control Pack (FACP-11)
Introduction:
The FACP-11 Auto Setting Controll Pack is capable of controlling the actuator's open/close degree over a resolution of 200:1 by a control signal of 4-20mA dc or 2-10vdc.
Features & Specifications
Features:
Needless to adjust- fully automated
High rangeability of control - over 200:1 resolution
Additional function
1. Fail mode (upon control signal loss)
• Open - fail to open • Stop - fail to stop
• Close -fail to close
2. Self checking function
• checking for limit switch • checking for pot
• checking for motor
3.lectronic brake control
4. feedback output : 4~20mA 1%DC(RL:250ohm)
5.small & lightweight
Electrical Specifications:
Power: 110vac or 220vac 50/60Hz
Control Signal Input : 4~ 20mA dc or 2~10vdc
Output Sibnal : 4~20mA 1%DC(RL:250ohm)
Calibration: Auto setting
Resolution: over 200
Power consumption:
Max 150W @110vac or 200W @220vac
Operation

Our modulating module is equipped with a blockage protection feature. If the actuator encounters a blockage, the module will automatically shut off the motor approximately 7 seconds after detection. Simultaneously, the yellow indicator lamp will flash rapidly, signaling that the actuator has entered Blockage Protection Mode.
To exit this mode, a reverse input signal must be provided. Upon receiving this signal, the actuator will deactivate the Blockage Protection Mode and resume normal operation.
1.Indicator explanations:
•Green Lamp On - Actuator is Opening
•Yellow Lamp On - Actuator is Operating
•Yellow Lamp Flashing Slowly - fully open/closed
•Yellow Lamp Flashing Quickly - Fail check limit switch, potentiometer, etc.
•Red Lamp On - Actuator is Closing
2.Auto Setting Switch:
Press and hold the Auto Setting Switch for 3 seconds to start the actuator's auto-calibration, where it cycles twice to find and confirm its open and close limit positions for precise operation.
3.Mode Switch Operation & Setting:

4. Output Adjust VR:
Fine-tune the "feedback output" for precise adjustment.
5. Limit Switch:
Input terminal where the digital limit is activated, indicated as "A."
• Limit switch common • Close limit switch • Open limit switch
6. Motor & Potentiometer
• Motor common • Open motor • Close motor • Ground
• Potentiometer P1 • Potentiometer P2 • Potentiometer P3